中欧体育官网,中欧体育

Language:Chinese | English

招标采购 >

3.6/6kV~26/35kV cross-linked polyethylene insulated power cableProduct number:YJV~YJV73 3.6/6~26/35
Advisory

Product Usage:

This product is suitable for power frequency distribution voltage 3.6 /6kV ~ 26 / 35kV transmission and distribution lines.

Implementation standards :

Implementation of GB / T12706.2 andGB / T12706.3 standards.

For flame-retardant, low-halogenlow-smoke flame-retardant, halogen-free low smoke flame retardant series ofpower cables, but also the implementation of GB / T19666, the flame retardantproperties in line with GB / T 18380 requirements;

For anti-termite cable power cableits anti-termite properties in line with JB / T 10696.9 requirements.


Type:

Note:For flame-retardant power cable, “Z(ZA-、ZB-、ZC-)” is added before the above type number;anti-termite power cable, "FY-" is added before the abovetype number;intelligent on-line temperature monitoring cable, "DFTS-"is added before the above type number.

 

1、single-corearmored cable for the exchange system, should be non-magnetic material armored.

 

Product specifications:

Use features:

1、rated temperature

Long-term maximum allowable operatingconductor temperature: 90 °C,Maximum operating temperature under short-timeoverload: 130°C,Maximum operating temperature under short circuit (shortcircuit duration 5 s): 250 °C

 

2、required

2.1 Cablelaying shall not be restricted by drop height; theambient temperature for laying shall not be lower than 0 °C, and if the ambienttemperature is lower than 0 °C, the cable shall be pre-heated

 

2.2 Minimum allowable bending radius for cable installation

Advisory In order to more attentive service to you, please fill in the complete question.